Once connected by the operator, the Clinton FL-20A makes all necessary adjustments and determines the location of a failure. This removes the need for specialized training by operators and let anyone easily use the equipment.

Key Features:

  • The digital FL-20A automates cable fault detection, reducing the time and training required to find problems.
  • Detects opens, metallic shorts, or high voltage shorts between conductors or between conductor and shield.
  • Quick and easy pinpointing of faults.
  • Simple operation:
    • Connect the FL-20A test probes to each end of the cable under test.
    • Enter the cable length on the digital touch screen.
    • Select “Shorts” or “Opens” to begin the test.
  • Rapid calculation of fault site distance from each test probe.
  • Displays fault location in feet or meters.
  • Provides a suggested trim area.
  • Faults can be cut out or repaired, salvaging the remaining good product and resulting in significant savings.

Sample display screens:

  • The FL-20A Cable Fault Locator:
    • Dimensions(cm): 31.8W x 35.56D x 25.4H
    • Weight: 17.2KG.
  • Smaller and lighter than predecessors.
  • Promises a great return on investment by salvaging expensive cable assemblies and lowering costs associated with salvage.

Major Features:

  • Identify Shorts/High Voltage Shorts/Opens
  • Fully Automated
  • Compact and Lightweight
PARAMETERVALUE
Test Voltage Range500v-20kV
Test FrequencyDC
Voltage Display6-inch backlit color TFT touch screen ​Accuracy 2% of reading
Fault IndicationTouch Screen Display , Open - A condition where a single conductor has no continuity from one end to the other.
Fault DefinitionsMetallic Short - Two conductors without insulation or. a conductor and a shield that physically come into contact with one another.
High-Voltage Short - Two conductors or a conductor and a shield which have no insulation between them but do not contact one another.
Power Requirements100-240 volta AC, 50/60 Hz 2 amps
Output Power6mA Maximum 
Equipment AccuracyBetter than 1% of total cable length (dependent on accuracy of actual cable footage and product uniformity).
Cable Loop ResistanceMetallic Short - 50 milliohms minimum , High-Voltage Short - 300 milliohms minimum